Guide · Conduit & connectors

Liquid-tight conduit fill chart: how many THHN conductors fit in LFNC-B

Conduit fill is a simple area calculation, but the LFNC-B numbers are different from EMT and PVC because the internal diameter is different. Here are the internal areas, the 40% fill limit and a ready-reckoner for THHN/THWN conductors.

The rule

NEC Chapter 9, Table 1 allows a raceway to be filled to 53% of its internal area with one conductor, 31% with two conductors, and 40% with three or more. The internal area of each LFNC-B trade size comes from Chapter 9, Table 4 (Article 356 section); conductor areas come from Table 5. Note 4 to Table 1 also allows the next-higher whole number of conductors when the calculation lands at 0.8 or more.

LFNC-B internal area and 40% fill

Trade size
Total internal area (in²)
40% fill (3+ wires)
31% fill (2 wires)
53% fill (1 wire)
3/8″
0.192
0.077
0.059
0.102
1/2″
0.314
0.125
0.097
0.166
3/4″
0.541
0.216
0.168
0.287
1″
0.873
0.349
0.270
0.462
1-1/4″
1.528
0.611
0.474
0.810
1-1/2″
1.981
0.792
0.614
1.050
2″
3.246
1.298
1.006
1.720

Maximum THHN / THWN / THWN-2 conductors (all the same size)

Conductor
Area (in²)
3/8″
1/2″
3/4″
1″
1-1/4″
1-1/2″
2″
14 AWG
0.0097
8
13
22
36
63
81
134
12 AWG
0.0133
5
9
16
26
46
59
97
10 AWG
0.0211
3
6
10
16
29
37
61
8 AWG
0.0366
1
3
6
9
16
21
35
6 AWG
0.0507
1
1
4
7
12
15
25
4 AWG
0.0824
1
1
2
4
7
9
15
3 AWG
0.0973
1
1
1
3
6
8
13
2 AWG
0.1158
—
1
1
3
5
7
11
1 AWG
0.1562
—
1
1
1
4
5
8
Values are computed from the Table 4 (LFNC-B) and Table 5 (THHN/THWN) figures shown, applying the 53/31/40% limits and the 0.8 rounding rule. Confirm against the NEC edition adopted in your jurisdiction — Table 4 for LFNC-B has been stable across recent editions, but always check. Mixed conductor sizes must be calculated by summing areas.

Worked example: pool pump

A 240-volt pool pump on a 20-amp circuit needs two 12 AWG hots and a 12 AWG equipment grounding conductor: three conductors × 0.0133 in² = 0.0399 in². The 40% limit for 1/2″ LFNC-B is 0.125 in², so 1/2″ liquid-tight is fine, with plenty of room to add a second pump circuit later. In practice many installers choose 3/4″ for pulling ease and future capacity.

Worked example: 3-ton condenser

A condensing unit on a 40-amp circuit with 8 AWG copper: two 8 AWG hots plus a 10 AWG ground = 2 × 0.0366 + 0.0211 = 0.0943 in². That is under the 1/2″ limit of 0.125 in², so 1/2″ works on paper, but a 3/4″ whip is the usual choice: the disconnect knockouts are typically 3/4″ and the pull is easier.

Other things that limit fill

  • Derating. More than three current-carrying conductors in a raceway triggers ampacity adjustment (310.15(C)). Fill may allow 9 wires; the ampacity table may not.
  • Pull length and bends. LFNC is limited to 360° of bends between pull points; long runs with many wires pull hard through flexible conduit.
  • Connector throat. The liquid-tight connector’s inside diameter is smaller than the conduit; check that the bundle passes the fitting.

Parts

Need a part number or a quote? Our sales team in Elizabeth, NJ will come back to you with availability and pricing.

Request a quote

Published by Superflex Ltd., manufacturer of Sealproof® and Rollerflex® products in Elizabeth, New Jersey since 1981. This guide is general information for installers and specifiers; always follow the current edition of the NEC as adopted in your jurisdiction, the product listing and the manufacturer instructions.